B18報警消息
報警消息和其他消息將發送到HIS和日志文件。 HIS上顯示的消息包括日期/時間戳,控制器位號名,生成的錯誤和其他消息。
以下是Exasmoc消息的列表。
表B 18.1 Exasmoc消息
No. | 消息格式 | 動作 |
---|---|---|
81 | Bad CON File Format (壞的CON文件格式) | CON文件格式與當前版本不對應。重新創建定義文件。 |
83 | Exasmoc controller is OnlineTuning(Exasmoc控制器在線Tuning中)。 | 已執行在線Tuning。 |
111 | SMOCPro Kernel %s: Initialized (SMOCPro內核%s:初始化)。 | 控制器已初始化。控制器初始化為CON文件和DEF文件的內容。工作區也被復位。 |
121 | Status is moved Opt to Control due to lack of EF(由于缺少EF,狀態將由Opt切換到Control)。 | 由于缺少EF變量,控制模式已從OPTIMIZE更改為CONTROL。 |
122 | EF ignored due to un-initialised variables(由于未初始化變量,EF被忽略)。 | 由于經濟函數基于未初始化的變量,因此未進行優化。選擇有效的EF函數。 |
131 | Wrong Plot Point Dimensions(錯誤的繪圖點尺寸)。 | 繪圖點不正確。使用PCTP重新創建控制器。 |
141 | [%s] MV %s has bad input and is not used([%s] MV%s的輸入有誤,未使用)。 | MV變量的值或質量不正確。確認MV位號名和值。 |
142 | [%s] POV %s has bad input and is not used([%s] POV%s的輸入有誤,未使用)。 | POV變量的值或質量不正確。 |
143 | [%s] DV %s has bad input and is not used([%s] DV%s的輸入有誤,未使用)。 | 確認DV位號名和值。 |
151 | MV [%s] setpoint Readback is outside tolerance range and will be used (SP/SPRB: [%s]).(MV [%s]設定值回讀超出公差范圍并將使用(SP / SPRB:[%s]))。 | 警告:MV [%s]的setpoint Readback與上一個MV輸出值的差值大于MV容差。回讀值仍將實現并在預測中使用。 |
152 | MV [%s] Readback %s is outside move range and will NOT be used (SP/SPRB: [%s]).(MV [%s]回讀%s在動作范圍外,不使用(SP / SPRB:[%s]))。 | 錯誤:MV[%s]的setpoint Readback與之前MV輸出值的差值超過允許的MV動作幅度。MV回讀值將不被用于下一次控制計算,控制器將會退出到Standby狀態。 |
161 | Failed to solve the optimization problem"(無法解決優化問題)。 | 優化進程失敗。保留前一個值。 |
162 | Failed to solve the static control feasibility problem(無法解決靜態控制的可行性問題)。 | 靜態可行性控制計算過程失敗。保留前一個值。 |
170 | [CALC] Input Tag (%s) is BAD. All dependent CALC will fail( [CALC]輸入位號(%s)為BAD。所有相關的CALC將失敗)。 | 計算中的輸入位號質量不佳。確認輸入的位號值和質量碼。 |
171 | [CALC] Calculation (%s) is BAD([CALC]計算(%s)為BAD)。 | 計算輸出位號的質量代碼為BAD。同上。 |
201 | Unable to write debug file (無法寫入debug文件)。 | 無法創建debug文件。發生內部錯誤時,請與產品服務聯系。 |
231 | [%s] Essential DV %s is not available ([%s]必須的DV%s不可用)。 | 必須的DV無效。當無效狀態持續超過最大關閉控制時間時,控制器將變為INACTIVE。 |
原文:
B17. Documentation View
By clicking “Document / Exasmoc” on the tree view, Exasmoc instruction manual is displayed.
When you read documents, it is necessary to install Adobe Reader in advance.
B18. Alarm Messages
Alarm Messages and other messages are sent to HIS and log file. Messages displayed on the HIS consist of date/time stamp, controller tag name, which generates error and other message.
Following is the list of Exasmoc messages.
Table B 18.1 Exasmoc Messages
No. | Message Format | Actions |
---|---|---|
81 | Bad CON File Format | CON file format is not corresponding to the current revision. Recreate the definition file again. |
83 | Exasmoc controller is OnlineTuning | Online tuning has executed. |
111 | SMOCPro Kernel %s: Initialized | The controller has initialized. The controller is initialized to the contents of CON file and DEF file. Work area is also reset. |
121 | Status is moved Opt to Control due to lack of EF | Control mode has changed to CONTROL from OPTIMISE due to the lack of EF variable. |
122 | EF ignored due to un-initialised variables | As the Economic Function is based on the un-initialized variable, the optimization was not done. Select the effective EF function. |
131 | Wrong Plot Point Dimensions | The plot point is not correct. Re-create the controller using PCTP again. |
141 | [%s] MV %s has bad input and is not used | The value or quality of the MV variable is not proper. Confirm the MV tag name and value. |
142 | [%s] POV %s has bad input and is not used | The value or quality of the POV variable is not proper. |
143 | [%s] DV %s has bad input and is not used | Confirm the DV tag name and value. |
/SPRB: [%s]). | Warning: The setpoint Readback for MV [%s] differs from the previous MV output value by more than the MV tolerance. The Readback value will still be implemented and used in the predictions. | |
152 | MV [%s] Readback %s is outside move range and will NOT be used (SP/SPRB: [%s]). | Error: The setpoint Readback for MV [%s] differs from the previous MV output value by more than the allowable MV move range. The MV Readback will not be used for the next control calculation and the controller will shed to Standby. |
161 | Failed to solve the optimization problem" | The optimization process was failed. The previous value remains. |
162 | Failed to solve the static control feasibility problem | The static feasibility control calculation process was failed. The previous value remains. |
170 | [CALC] Input Tag (%s) is BAD. All dependent CALC will fail | The input tag quality in the Calculation is Bad. Confirm the input tag value and quality code. |
171 | [CALC] Calculation (%s) is BAD | The quality code of calculation output tag is BAD. Same above. |
201 | Unable to write debug file | Cannot create the debug file. As the internal error occurred, contact with Product Service. |
231 | [%s] Essential DV %s is not available | The essential DV is invalid. When the invalid status continues more that the Maximum Time Off Control, the controller becomes INACTIVE. |